Liquid-Tight Flexible Steel Conduit

Product Introduction and Applications: 
Liquid-tight Flexible Steel Conduit is a raceway of circular cross section having an outer liquidtight, nonmetallic, sunlight-resistant jacket over an inner flexible metal core with associated couplings, connectors, and fittings for the installation of electric conductors. 
Liquidtight flexible metal conduit (LFMC) is intended for  use in wet locations or where exposed to mineral oil, both at a maximum temperature of 140°C.
LFMC shall be permitted to be used in exposed or concealed  locations as follows:
• Where conditions of installation, operation, or maintenance require flexibility or protection from liquids, vapors, or solids
• As permitted by 501.10(B), 502.10, 503.10, and 504.20 and in other hazardous (classified) locations where specifically approved, and by 553.7(B)
• For direct burial where listed and marked for the purpose
Features:
• Protection for wiring circuits located in extremely wet or damp areas
• Suitable for machines and equipment where ruggedness is required
• For use on presses, welders, pumps, blowers, grinders,conveyors, automated lines
• Galvanized steel core for mechanical protection
• Abrasion resistant PVC jacket won’t wrinkle or shrink from cut ends
• Exceptional crush proof quality
• Smooth interior for easy wire pull-through
• Complete protection against most liquids and moisture vapor
• Resists sunlight, heat, oil and chemical degradation 
• Rated: -20° C to +60° C (-5° F to +140° F)
• Accepts standard UL Listed liquid-tight connectors
• Superior protection for circuits located in hostile environments
• Installs quickly and easily from handy payout carton
 
NEC Articles:
• Article 250.118 Equipment Grounding
• Article 300.22 Air Plenum
• Article 350 Liquidtight Flexible Metal Conduit
• Article 501.10, Class I, Div. 2:Classes II and III
• Article 502.10, Class II, Div. 1 & 2
• Article 503.10, Class III, Div. 1&2
• Article 511.7, Above Class l Locations
• Article 620.21 Elevators, Escalators and Platform Lifts
• Article 645.5 Information Technology Equipment
• Article 680.42 Pools, Hot Tubs and Fountains
• Article 695.6 Electrical Fire Pump
 

 


SPECIFICATIONS
Size (inch) Inside Diameter Outside Diameter P.V.C Jacket Thickness Min.Bending Radius (mm.) Lenght of Each Roll
Min(mm) Max (mm) Min(mm) Max (mm) Min(mm) Max (mm) (Ft.) (m.)
1/2'' 15.70 16.30 20.80 21.30 1.00 1.35 70 100 30
3/4'' 20.70 21.30 26.00 26.70 1.10 1.55 100 100 30
1'' 26.20 26.90 32.70 33.40 1.70 1.95 180 100 30
1 1/4'' 35.10 35.70 41.50 42.20 1.25 1.70 200 50 15
1 1/2'' 40.20 40.80 47.40 48.30 1.80 2.30 250 50 15
2'' 51.00 51.80 59.40 60.30 2.40 2.80 450 50 15
2 1/2'' 62.50 64.00 72.10 73.00 2.00 2.50 550 25 7.5
3'' 77.60 78.80 87.70 88.90 2.50 3.20 800 25 7.5
4'' 101.10 102.50 113.20 114.30 2.80 3.03 1200 25 7.5