BACK

Insulated Metallic Conduit Bushing

Use:
Used to terminate Rigid and IMC conduit to a box or enclosure and to provide a smooth pulling surface. Plastic insuliner prevents damage to wire insulation. Insuliner rated at 150°C.
Material/Finish: 
Die Cast â€‹Zinc
Applicable Third Party Standards:
UL Standard: 514B
NEMA: FB-1
UL File No: E358457

Catalog Number Trade Size (in) Max.Size (in)
A B
E-L 52 IM ½'' 1.06 .43
E-L 60 IM ¾''  1.31 .43
E-L 61 IM 1'' 1.59 .48
E-L 65 IM 1 ¼'' 1.96 .56
E-L 69 IM 1 ½'' 2.18 .60
E-L 75 IM 2'' 2.68 .56
E-L 76 IM 2 ½'' 3.25 .90
E-L 90 IM 3'' 3.87 .85
E-L 91 IM 3 ½'' 4.37 .93
E-L 92 IM 4'' 5.00 .93
E-L 95 IM 5'' 6.06 1.31
E-L 96 IM 6'' 7.25 1.31
*Non-insulated models are available.
Please consult factory for details.

 